We rely upon strategic thinking, constant modernisation in all segments, technological advances and of course upon our employees that directly participate inside our success for heat recovery core , Air Sterilization , Energy Recovery Ventilation System , Our products are widely used in many industrial fields. Our Company Services Division in good faith for the purpose of the quality of survival. All for customer service.
Quality Inspection for China Supplier Plate Heat Exchanger Core - Liquid Circulation Heat Exchangers – Holtop Detail:

Liquid Circulation Heat Exchanger -Heat recovery core of AHU

Working Principle

Liquid circulation heat exchanger is liquid to air heat exchanger, heat exchangers usually installed in both fresh air (OA) side and exhaust air (EA) side, the pump between the two heat exchangers make the liquid circulate, then the heat in the liquid pre-heat or pre-cool the fresh air. Normally the liquid is water, but In winter, in order to decrease the freezing point, moderate ethylene glycol will be added into the water in reasonable percentage.

Features of Holtop Liquid Circulation Heat Exchanger

(1) Fresh air and exhaust air heat exchanged by separated liquid pipes, zero cross contamination. It suitable for heat recovery energy saving of air handling system of hospital, germfree lab and industries which discharge poisonous and harmful gas.

(2) Stable,reliable and long service life

(3) Flexible connection between fresh air and exhaust air exchangers, easy installation, which also is convenient for old AHU improvement.

(4) Heat exchangers are conventional, easy and low maintenance costs.

(5) Wide range of application, various connection methods like one to one, one to more, or many to many.

Specifications  

(1) Liquid circulation heat exchangers is sensible heat exchangers, efficiency is between 55% to 60%.

(2) Suggested rows number in 6 or 8, face velocity not over 2.8 m/s

(3) The choice of circulating pump can refer to the fresh air and exhaust air pressure drop and the water flows pressure drop.

(4) Air flow direction has significant effect on the heat recovery efficiency, influence rate up to 20%.

(5) Freezing point of the hybrid ethylene glycol and water should be 4-6 ℃ lower than the local minimum outdoor temperature of winter, percentage of hybrid can be referred to the following table.

Freezing point -1.4 - 1.3 -5.4 -7.8 -10.7 -14.1 -17.9 -22.3
Weight percentage (%) 5 10 15 20 25 30 35 40
Volume percentage (%) 4.4 8.9 13.6 18.1 22.9 27.7 32.6 37.5
  • Previous: Combine Air Handling Units AHU
  • Next: Heat Pipe Heat Exchangers

Product detail pictures:

Quality Inspection for China Supplier Plate Heat Exchanger Core -
 Liquid Circulation Heat Exchangers – Holtop detail pictures


Related Product Guide:

Our organization sticks to your principle of "Quality may be the life of your organization, and reputation will be the soul of it" for Quality Inspection for China Supplier Plate Heat Exchanger Core - Liquid Circulation Heat Exchangers – Holtop , The product will supply to all over the world, such as: Japan , London , UK , Establish long term and win-win business relationships with all our customers, share the success and enjoy the happiness of spreading our products to the world together. Trust us and you will gain more. Please feel free to contact us for more information, we assure you of our best attention at all times.
  • The supplier cooperation attitude is very good, encountered various problems, always willing to cooperate with us, to us as the real God.
    5 Stars By Delia Pesina from Cannes - 2018.09.23 18:44
    The product classification is very detailed that can be very accurate to meet our demand, a professional wholesaler.
    5 Stars By James Brown from Estonia - 2018.12.25 12:43
    Write your message here and send it to us