language

Good Quality Heat Exchanger - Liquid Circulation Heat Exchangers – Holtop

Products Detail
We believe in: Innovation is our soul and spirit. High-quality is our life. Consumer need to have is our God for climate control , Cleanroom heat exchanger , Heat recovery units , Should you be fascinated in any of our products and services, remember to do not hesitate to make contact with us. We're ready to reply you inside of 24 several hours soon after receipt of one's ask for and also to develop mutual un-limited advantages and organization in around potential.
Good Quality Heat Exchanger - Liquid Circulation Heat Exchangers – Holtop Detail:

Liquid Circulation Heat Exchanger -Heat recovery core of AHU

Working Principle

Liquid circulation heat exchanger is liquid to air heat exchanger, heat exchangers usually installed in both fresh air (OA) side and exhaust air (EA) side, the pump between the two heat exchangers make the liquid circulate, then the heat in the liquid pre-heat or pre-cool the fresh air. Normally the liquid is water, but In winter, in order to decrease the freezing point, moderate ethylene glycol will be added into the water in reasonable percentage.

Features of Holtop Liquid Circulation Heat Exchanger

(1) Fresh air and exhaust air heat exchanged by separated liquid pipes, zero cross contamination. It suitable for heat recovery energy saving of air handling system of hospital, germfree lab and industries which discharge poisonous and harmful gas.

(2) Stable,reliable and long service life

(3) Flexible connection between fresh air and exhaust air exchangers, easy installation, which also is convenient for old AHU improvement.

(4) Heat exchangers are conventional, easy and low maintenance costs.

(5) Wide range of application, various connection methods like one to one, one to more, or many to many.

Specifications  

(1) Liquid circulation heat exchangers is sensible heat exchangers, efficiency is between 55% to 60%.

(2) Suggested rows number in 6 or 8, face velocity not over 2.8 m/s

(3) The choice of circulating pump can refer to the fresh air and exhaust air pressure drop and the water flows pressure drop.

(4) Air flow direction has significant effect on the heat recovery efficiency, influence rate up to 20%.

(5) Freezing point of the hybrid ethylene glycol and water should be 4-6 ℃ lower than the local minimum outdoor temperature of winter, percentage of hybrid can be referred to the following table.

Freezing point -1.4 - 1.3 -5.4 -7.8 -10.7 -14.1 -17.9 -22.3
Weight percentage (%) 5 10 15 20 25 30 35 40
Volume percentage (%) 4.4 8.9 13.6 18.1 22.9 27.7 32.6 37.5
  • Previous: Combine Air Handling Units AHU
  • Next: Heat Pipe Heat Exchangers

Product detail pictures:

Good Quality Heat Exchanger -
 Liquid Circulation Heat Exchangers – Holtop detail pictures


Related Product Guide:

We are convinced that with joint efforts, the business between us will bring us mutual benefits. We can assure you product quality and competitive price for Good Quality Heat Exchanger - Liquid Circulation Heat Exchangers – Holtop , The product will supply to all over the world, such as: Morocco , Pakistan , Nigeria , Our team knows well the market demands in different countries, and is capable of supplying suitable quality products at the best prices to different markets. Our company has already set up a professional, creative and responsible team to develop clients with the multi-win principle.
  • After the signing of the contract, we received satisfactory goods in a short term, this is a commendable manufacturer.
    5 Stars By Edith from New York - 2018.06.09 12:42
    With a positive attitude of "regard the market, regard the custom, regard the science", the company works actively to do research and development. Hope we have a future business relationships and achieving mutual success.
    5 Stars By Leona from The Swiss - 2018.09.29 17:23
    Write your message here and send it to us