Quality Inspection for China Supplier Plate Heat Exchanger Core - Liquid Circulation Heat Exchangers – Holtop Detail:
Liquid Circulation Heat Exchanger -Heat recovery core of AHU
Working Principle
Liquid circulation heat exchanger is liquid to air heat exchanger, heat exchangers usually installed in both fresh air (OA) side and exhaust air (EA) side, the pump between the two heat exchangers make the liquid circulate, then the heat in the liquid pre-heat or pre-cool the fresh air. Normally the liquid is water, but In winter, in order to decrease the freezing point, moderate ethylene glycol will be added into the water in reasonable percentage.
Features of Holtop Liquid Circulation Heat Exchanger
(1) Fresh air and exhaust air heat exchanged by separated liquid pipes, zero cross contamination. It suitable for heat recovery energy saving of air handling system of hospital, germfree lab and industries which discharge poisonous and harmful gas.
(2) Stable,reliable and long service life
(3) Flexible connection between fresh air and exhaust air exchangers, easy installation, which also is convenient for old AHU improvement.
(4) Heat exchangers are conventional, easy and low maintenance costs.
(5) Wide range of application, various connection methods like one to one, one to more, or many to many.
Specifications
(1) Liquid circulation heat exchangers is sensible heat exchangers, efficiency is between 55% to 60%.
(2) Suggested rows number in 6 or 8, face velocity not over 2.8 m/s
(3) The choice of circulating pump can refer to the fresh air and exhaust air pressure drop and the water flows pressure drop.
(4) Air flow direction has significant effect on the heat recovery efficiency, influence rate up to 20%.
(5) Freezing point of the hybrid ethylene glycol and water should be 4-6 ℃ lower than the local minimum outdoor temperature of winter, percentage of hybrid can be referred to the following table.
Freezing point | -1.4 | - 1.3 | -5.4 | -7.8 | -10.7 | -14.1 | -17.9 | -22.3 |
Weight percentage (%) | 5 | 10 | 15 | 20 | 25 | 30 | 35 | 40 |
Volume percentage (%) | 4.4 | 8.9 | 13.6 | 18.1 | 22.9 | 27.7 | 32.6 | 37.5 |
- Previous: Combine Air Handling Units AHU
- Next: Heat Pipe Heat Exchangers
Product detail pictures:
Related Product Guide:
Our firm has been concentrating on brand strategy. Customers' satisfaction is our best advertising. We also offer OEM provider for Quality Inspection for China Supplier Plate Heat Exchanger Core - Liquid Circulation Heat Exchangers – Holtop , The product will supply to all over the world, such as: Nigeria , Tunisia , Karachi , For anyone who is keen on any of our goods right after you view our product list, please really feel absolutely free to get in touch with us for inquiries. You are able to send us emails and contact us for consultation and we shall respond to you as soon as we can. If it's easy, you may locate out our address in our web-site and come to our business for far more information of our products by your self. We are always ready to construct extended and steady co-operation relations with any possible customers in the related fields.
By Ricardo from Turin - 2017.11.29 11:09
The after-sale warranty service is timely and thoughtful, encounter problems can be resolved very quickly, we feel reliable and secure.
By Octavia from Brasilia - 2017.04.08 14:55