Quality Inspection for China Supplier Plate Heat Exchanger Core - Liquid Circulation Heat Exchangers – Holtop Detail:
Liquid Circulation Heat Exchanger -Heat recovery core of AHU
Working Principle
Liquid circulation heat exchanger is liquid to air heat exchanger, heat exchangers usually installed in both fresh air (OA) side and exhaust air (EA) side, the pump between the two heat exchangers make the liquid circulate, then the heat in the liquid pre-heat or pre-cool the fresh air. Normally the liquid is water, but In winter, in order to decrease the freezing point, moderate ethylene glycol will be added into the water in reasonable percentage.
Features of Holtop Liquid Circulation Heat Exchanger
(1) Fresh air and exhaust air heat exchanged by separated liquid pipes, zero cross contamination. It suitable for heat recovery energy saving of air handling system of hospital, germfree lab and industries which discharge poisonous and harmful gas.
(2) Stable,reliable and long service life
(3) Flexible connection between fresh air and exhaust air exchangers, easy installation, which also is convenient for old AHU improvement.
(4) Heat exchangers are conventional, easy and low maintenance costs.
(5) Wide range of application, various connection methods like one to one, one to more, or many to many.
Specifications
(1) Liquid circulation heat exchangers is sensible heat exchangers, efficiency is between 55% to 60%.
(2) Suggested rows number in 6 or 8, face velocity not over 2.8 m/s
(3) The choice of circulating pump can refer to the fresh air and exhaust air pressure drop and the water flows pressure drop.
(4) Air flow direction has significant effect on the heat recovery efficiency, influence rate up to 20%.
(5) Freezing point of the hybrid ethylene glycol and water should be 4-6 ℃ lower than the local minimum outdoor temperature of winter, percentage of hybrid can be referred to the following table.
Freezing point | -1.4 | - 1.3 | -5.4 | -7.8 | -10.7 | -14.1 | -17.9 | -22.3 |
Weight percentage (%) | 5 | 10 | 15 | 20 | 25 | 30 | 35 | 40 |
Volume percentage (%) | 4.4 | 8.9 | 13.6 | 18.1 | 22.9 | 27.7 | 32.6 | 37.5 |
- Previous: Combine Air Handling Units AHU
- Next: Heat Pipe Heat Exchangers
Product detail pictures:
Related Product Guide:
We can constantly satisfy our respected customers with our good high quality, good price tag and good support due to we have been additional specialist and extra hard-working and do it in cost-effective way for Quality Inspection for China Supplier Plate Heat Exchanger Core - Liquid Circulation Heat Exchangers – Holtop , The product will supply to all over the world, such as: Boston , Plymouth , Borussia Dortmund , We welcome you to visit our company & factory and our showroom displays various products and solutions that will meet your expectations. Meanwhile, it is convenient to visit our website. Our sales staff will try their best to supply you with the best services. If you will need more information, please do not hesitate to contact us via E-mail, fax or telephone.
By Ivan from Morocco - 2018.06.18 19:26
Perfect services, quality products and competitive prices, we have work many times, every time is delighted, wish continue to maintain!
By Harriet from Albania - 2017.09.16 13:44