Quality Inspection for China Supplier Plate Heat Exchanger Core - Liquid Circulation Heat Exchangers – Holtop Detail:
Liquid Circulation Heat Exchanger -Heat recovery core of AHU
Working Principle
Liquid circulation heat exchanger is liquid to air heat exchanger, heat exchangers usually installed in both fresh air (OA) side and exhaust air (EA) side, the pump between the two heat exchangers make the liquid circulate, then the heat in the liquid pre-heat or pre-cool the fresh air. Normally the liquid is water, but In winter, in order to decrease the freezing point, moderate ethylene glycol will be added into the water in reasonable percentage.
Features of Holtop Liquid Circulation Heat Exchanger
(1) Fresh air and exhaust air heat exchanged by separated liquid pipes, zero cross contamination. It suitable for heat recovery energy saving of air handling system of hospital, germfree lab and industries which discharge poisonous and harmful gas.
(2) Stable,reliable and long service life
(3) Flexible connection between fresh air and exhaust air exchangers, easy installation, which also is convenient for old AHU improvement.
(4) Heat exchangers are conventional, easy and low maintenance costs.
(5) Wide range of application, various connection methods like one to one, one to more, or many to many.
Specifications
(1) Liquid circulation heat exchangers is sensible heat exchangers, efficiency is between 55% to 60%.
(2) Suggested rows number in 6 or 8, face velocity not over 2.8 m/s
(3) The choice of circulating pump can refer to the fresh air and exhaust air pressure drop and the water flows pressure drop.
(4) Air flow direction has significant effect on the heat recovery efficiency, influence rate up to 20%.
(5) Freezing point of the hybrid ethylene glycol and water should be 4-6 ℃ lower than the local minimum outdoor temperature of winter, percentage of hybrid can be referred to the following table.
Freezing point | -1.4 | - 1.3 | -5.4 | -7.8 | -10.7 | -14.1 | -17.9 | -22.3 |
Weight percentage (%) | 5 | 10 | 15 | 20 | 25 | 30 | 35 | 40 |
Volume percentage (%) | 4.4 | 8.9 | 13.6 | 18.1 | 22.9 | 27.7 | 32.6 | 37.5 |
- Previous: Combine Air Handling Units AHU
- Next: Heat Pipe Heat Exchangers
Product detail pictures:
Related Product Guide:
Bear "Customer initially, High-quality first" in mind, we work closely with our prospects and supply them with efficient and specialist companies for Quality Inspection for China Supplier Plate Heat Exchanger Core - Liquid Circulation Heat Exchangers – Holtop , The product will supply to all over the world, such as: Sri Lanka , Swiss , Poland , Our objective is "to supply first step products and best service for our customers, thus we are sure you must have a margin benefit through cooperating with us". If you are interested in any of our products or would like to discuss a custom order, please feel free to contact us. We are looking forward to forming successful business relationships with new clients around the world in the near future.
By Karen from Cologne - 2017.12.02 14:11
Good quality and fast delivery, it's very nice. Some products have a little bit problem, but the supplier replaced timely, overall, we are satisfied.
By Carey from Berlin - 2017.12.09 14:01