We insist on offering premium quality manufacturing with superior business concept, honest product sales as well as finest and fast assistance. it will bring you not only the good quality product or service and huge profit, but the most significant is to occupy the endless market for heat recovery ventilator , Ventilation System heat recovery core , air conditioners , We have now four leading solutions. Our products are most effective sold not only during the Chinese market, but also welcomed during the international industry.
Quality Inspection for China Supplier Plate Heat Exchanger Core - Liquid Circulation Heat Exchangers – Holtop Detail:

Liquid Circulation Heat Exchanger -Heat recovery core of AHU

Working Principle

Liquid circulation heat exchanger is liquid to air heat exchanger, heat exchangers usually installed in both fresh air (OA) side and exhaust air (EA) side, the pump between the two heat exchangers make the liquid circulate, then the heat in the liquid pre-heat or pre-cool the fresh air. Normally the liquid is water, but In winter, in order to decrease the freezing point, moderate ethylene glycol will be added into the water in reasonable percentage.

Features of Holtop Liquid Circulation Heat Exchanger

(1) Fresh air and exhaust air heat exchanged by separated liquid pipes, zero cross contamination. It suitable for heat recovery energy saving of air handling system of hospital, germfree lab and industries which discharge poisonous and harmful gas.

(2) Stable,reliable and long service life

(3) Flexible connection between fresh air and exhaust air exchangers, easy installation, which also is convenient for old AHU improvement.

(4) Heat exchangers are conventional, easy and low maintenance costs.

(5) Wide range of application, various connection methods like one to one, one to more, or many to many.

Specifications  

(1) Liquid circulation heat exchangers is sensible heat exchangers, efficiency is between 55% to 60%.

(2) Suggested rows number in 6 or 8, face velocity not over 2.8 m/s

(3) The choice of circulating pump can refer to the fresh air and exhaust air pressure drop and the water flows pressure drop.

(4) Air flow direction has significant effect on the heat recovery efficiency, influence rate up to 20%.

(5) Freezing point of the hybrid ethylene glycol and water should be 4-6 ℃ lower than the local minimum outdoor temperature of winter, percentage of hybrid can be referred to the following table.

Freezing point -1.4 - 1.3 -5.4 -7.8 -10.7 -14.1 -17.9 -22.3
Weight percentage (%) 5 10 15 20 25 30 35 40
Volume percentage (%) 4.4 8.9 13.6 18.1 22.9 27.7 32.6 37.5
  • Previous: Combine Air Handling Units AHU
  • Next: Heat Pipe Heat Exchangers

Product detail pictures:

Quality Inspection for China Supplier Plate Heat Exchanger Core -
 Liquid Circulation Heat Exchangers – Holtop detail pictures


Related Product Guide:

Our commission is to serve our users and clients with best quality and competitive portable digital products for Quality Inspection for China Supplier Plate Heat Exchanger Core - Liquid Circulation Heat Exchangers – Holtop , The product will supply to all over the world, such as: Cambodia , Karachi , Auckland , We seriously promise that we provide all the customers with the best quality products, the most competitive prices and the most prompt delivery. We hope to win a resplendent future for customers and ourselves.
  • Speaking of this cooperation with the Chinese manufacturer, I just want to say"well dodne", we are very satisfied.
    5 Stars By Kim from San Francisco - 2017.06.29 18:55
    This is a honest and trustworthy company, technology and equipment are very advanced and the prodduct is very adequate, there is no worry in the suppliment.
    5 Stars By Kevin Ellyson from Roman - 2018.09.16 11:31
    Write your message here and send it to us