Our advantages are lower prices,dynamic sales team,specialized QC,strong factories,high quality products and services for Customized Function Modules , fresh air purification , ventilation hygiene , On account of superior excellent and aggressive rate , we will be the sector leader, make sure you don’t hesitate to contact us by cellular phone or email, if you're fascinated in almost any of our items.
Quality Inspection for China Supplier Plate Heat Exchanger Core - Liquid Circulation Heat Exchangers – Holtop Detail:

Liquid Circulation Heat Exchanger -Heat recovery core of AHU

Working Principle

Liquid circulation heat exchanger is liquid to air heat exchanger, heat exchangers usually installed in both fresh air (OA) side and exhaust air (EA) side, the pump between the two heat exchangers make the liquid circulate, then the heat in the liquid pre-heat or pre-cool the fresh air. Normally the liquid is water, but In winter, in order to decrease the freezing point, moderate ethylene glycol will be added into the water in reasonable percentage.

Features of Holtop Liquid Circulation Heat Exchanger

(1) Fresh air and exhaust air heat exchanged by separated liquid pipes, zero cross contamination. It suitable for heat recovery energy saving of air handling system of hospital, germfree lab and industries which discharge poisonous and harmful gas.

(2) Stable,reliable and long service life

(3) Flexible connection between fresh air and exhaust air exchangers, easy installation, which also is convenient for old AHU improvement.

(4) Heat exchangers are conventional, easy and low maintenance costs.

(5) Wide range of application, various connection methods like one to one, one to more, or many to many.

Specifications  

(1) Liquid circulation heat exchangers is sensible heat exchangers, efficiency is between 55% to 60%.

(2) Suggested rows number in 6 or 8, face velocity not over 2.8 m/s

(3) The choice of circulating pump can refer to the fresh air and exhaust air pressure drop and the water flows pressure drop.

(4) Air flow direction has significant effect on the heat recovery efficiency, influence rate up to 20%.

(5) Freezing point of the hybrid ethylene glycol and water should be 4-6 ℃ lower than the local minimum outdoor temperature of winter, percentage of hybrid can be referred to the following table.

Freezing point -1.4 - 1.3 -5.4 -7.8 -10.7 -14.1 -17.9 -22.3
Weight percentage (%) 5 10 15 20 25 30 35 40
Volume percentage (%) 4.4 8.9 13.6 18.1 22.9 27.7 32.6 37.5
  • Previous: Combine Air Handling Units AHU
  • Next: Heat Pipe Heat Exchangers

Product detail pictures:

Quality Inspection for China Supplier Plate Heat Exchanger Core -
 Liquid Circulation Heat Exchangers – Holtop detail pictures


Related Product Guide:

The key to our success is "Good Product Quality, Reasonable Value and Efficient Service" for Quality Inspection for China Supplier Plate Heat Exchanger Core - Liquid Circulation Heat Exchangers – Holtop , The product will supply to all over the world, such as: Bolivia , Greece , Jordan , Since always, we adhering to the "open and fair, share to get, the pursuit of excellence, and creation of value"values, adhere to the"integrity and efficient, trade-oriented, best way , best valve" business philosophy. Together with our all over the world have branches and partners to develop new business areas, maximum common values. We sincerely welcome and together we share in global resources, opening up new career together with the chapter.
  • Production management mechanism is completed, quality is guaranteed, high credibility and service let the cooperation is easy, perfect!
    5 Stars By Jean from Florence - 2018.11.04 10:32
    Good quality and fast delivery, it's very nice. Some products have a little bit problem, but the supplier replaced timely, overall, we are satisfied.
    5 Stars By King from Bhutan - 2018.09.21 11:44
    Write your message here and send it to us